Test kit for boiler and cooling water: Nitrite, Chloride, P-Alkalinity and pH tests for marine systems
-
Some reagents required for tests shown in this booklet are classed as hazardous and as such, a minimum protection of gloves (rubber or plastic) and safety goggles/spectacles or facemask MUST BE WORN.
In addition please note and observe the Risk and Safety phrases on each reagent container and follow handling guidelines as instructed.
GENERAL NOTES
- Avoid contact with skin or eyes
- In case of contact with skin or eyes rinse immediately with plenty of running tap water, and seek medical attention
- Seek attention if irritation persists
- In case of ingestion, wash the mouth out thoroughly with water, try to vomit and seek medical attention
-
P-Alkalinity
-
Take 20 ml of cold coolingwater sample with the 20 ml syringe. Spray the 20 ml in the clean test jar.
-
Add 4 drops of Reagent PA1. The sample will turn pink. In case the sample does not colour pink, the reading is zero.
-
Add drop by drop Reagent PA2, until the sample decolours. Count the numbers of drops used.
-
Each drop is equivalent to 40 mg/l or ppm P-Alkalinity expressed as CaCO3
-
Retain the sample after the alkalinity test, as this sample can be used for the Chloride test.
P-Alkalinity Reference Drops of PA2 Reagent P-Alkalinity as mg/l CaCO3 Notes 1 40 Low P-Alkalinity, increase product dosage to achieve 200 mg/l P-Alkalinity 2 80 3 120 Correct P-Alkalinity 3 120 4 160 5 200 6 240 7 280 ←
Reduce P-Alkalinity by increased Top and Bottom blowdown and reduce dosing.9 360 8 320 Chloride Test
-
Take the 20 ml sample that is first used for the P-alkalinity test.
-
Add 12 drops of Reagent BC1. The sample will turn orange/yellow.
-
Add drop by drop Reagent BC2, until a turbid dark orange to brown colour appears. Count the numbers of drops used.
-
Each drop is equivalent to 20 mg/l or ppm Chlorides
Boilerwater Chloride Reference Drops of BC2 Reagent Chloride as mg/
l Cl-Notes 1 20 Maximum Chloride levels:
⇒ Low pressure boilers : 300 mg/l
⇒ Medium pressure boilers : 100 mg/l2 40 3 60 4 80 5 100 6 120 In case the chloride level is too high, reduce the amount of chlorides by blowdown. 7 140 8 160 9 180 10 200 11 220 12 240 13 260 14 280 15 300 ⇒ 1 mg/l is 1 ppm 16 320 17 340 18 360 19 380 20 400 Condensate pH Test (7,0 - 14,0)
-
Take 50 ml of cold condensate sample in the clean test jar.
-
Dip test strip for 1 second in the sample.
-
Shake off excess sample solution.
-
Compare with colour scale and read off the corresponding pH value.
Condensate pH Reference (7,0 – 14,0) pH value Status Action 7,0 Corrosive See fault finding chart 7,5 8,0 Slightly corrosive 8,5 9,0 Non corrosive Well treated 9,5 10,0 10,5 Corrosive on Cop-
perSee fault finding chart 11,0 11,5 12,0 12,5 Corrosive on Cop-
per and Iron13,0 13,5 14,0 -
-
Boilerwater Fault Finding Chart Fault Finding Chart Cause(s) Solution(s) Chlorides lower than 20 ppm Boiler newly filled with demineralized or evaporated water Boiler water has to concentrate, will take several days High blowdown Check blowdown valves for leakages
Chlorides far too high Low quality feed water Sea cooling water leakageOnly use demineralized or evaporated water Search for leakages, for example at the condenser
P-Alkalinity too low
Boiler newly filled with demineralized water Boilerwater has to concentrate, will take several days Low Caretreat 3 Boiler dosage Check dosingpump / increase dosage P-Alkalinity too high Low quality feed water Only use demineralized or evaporated water Do NOT use shorewaterHigh Caretreat 3 Boiler dosage Low blowdownCheck dosingpump / decrease dosage Increase blowdown, check for blocked blowdown valvespH Condensate too low
Low hotwell temperature Increase hotwell temperature to 80*C Low Caretreat 4 Boiler dosage Check dosing pump / increase dosage pH Condensate too highHigh cloride level in boiler pH Alkalinity too highSee: Chlorides far too high See: pH Alkalinity too highCarry over, causing wet steam Increase blowdown, check for blocked blowdown valves -
Chloride Test
-
Take 20 ml of cold coolingwater sample with the 20 ml syringe. Spray the 20 ml in the clean test jar.
-
Add 12 drops of Reagent BC1. The sample will turn orange/yellow.
-
Add drop by drop Reagent BC2, until a turbid dark orange to brown colour appears. Count the numbers of drops used.
-
Each drop is equivalent to 20 mg/l or ppm Chlorides
Coolingwater Chloride Reference Drops of BC2 Reagent Chloride as mg/
l Cl-Notes 1 20 2 40 3 60 4 80 Above 50 mg/l Chloride concentration; raise the nitrite level 100 ppm for every 10 mg/l chloride. 5 100 6 120 In case the chloride level is too high, reduce the amount of chlorides by partly refreshing the coolingwater with demineralized or evaporated water. After refreshing, repeat the Nitrite test. 7 140 8 160 9 180 10 200 11 220 12 240 13 260 14 280 15 300 ⇒ 1 mg/l is 1 ppm 16 320 17 340 18 360 19 380 20 400 Nitrite Test
-
Take 0,5 ml of cold coolingwater sample with the 2,5 ml syringe. Spray the 0,5 ml in the clean small test tube.
-
Add 4 drops of Reagent N1. The sample will turn dark orange/red.
-
Add drop by drop Reagent N2, until a pale blue colour appears. Count the numbers of drops used.
-
Each drop is equivalent to 200 mg/l or ppm Nitrite (NO2-)
Nitrite Reference Drops of N2 Reagent Nitrite as
mg/l NO -
21 200 2 400 3 600 4 800 5 1000 6 1200 7 1400 8 1600 9 1800 10 2000 11 2200 12 2400 13 2600 14 2800 15 3000 16 3200 17 3400 18 3600 19 3800 20 4000 Notes:
Maximum Chloride levels:
⇒ LT Systems : 100 mg/l
⇒ HT Systems : 50 mg/lIn case of too low Nitrite level dose Caretreat 2 Diesel. 1 liters per m3 gives 250 mg/l NO2-.
In case of too high Nitrite level partly refresh the coolingwater with demineralized or evaporated water. After refreshing, repeat the Nitrite test.
Initial Dosing Reference — Engine Type Engine type Chloride as
mg/l Cl-Nitrite as mg/l
NO -
2Initial Dosing
rate in l/m3HT Systems < 50 1500-2500 6 -10 HT Systems < 50 1500-2500 6 -10 LT Systems 50 - 100 1750-3000 7 - 12 Coolingwater pH Test (1,0 - 14,0) or (7,0 - 14,0)
-
Take 50 ml of cold coolingwater sample in the clean test jar.
-
Dip test strip for 1 second in the sample.
-
Shake off excess sample solution.
-
Compare with colour scale and read off the corresponding pH value.
Coolingwater pH Reference (1,0 – 14,0 or 7,0 – 14,0) pH value Status Action < 6,5 Corrosive to highly corro-
siveSee fault fin-
ding chart7,0 7,5 8,0 Slightly corrosive 8,5 9,0 Non corrosive Well treated 9,5 10,0 10,5 Corrosive on Copper and Aluminium See fault fin-
ding chart11,0 11,5 12,0 Corrosive on Iron, Copper and Aluminium 12,5 13,0 13,5 14,0 -
-
Coolingwater Fault Finding Chart Fault Finding Chart Cause(s) Solution(s) Chlorides far too high Low quality feed water Only use demineralized or evaporated water Sea cooling water leakage Search for leakage(s) Nitrites low Coolingwater leakageAdd Caretreat 2 DieselCoolingwater (partly) refreshed Add Caretreat 2 Diesel Nitrites remain low
Air intake in the systemCheck coolingwater pumpseals Check header/expansion tankExhaust gasses in the system
Check for leakages,
example leaking cylinder head
Bacteria in the system Check for slime deposits Add a non corrosive biocide, CaretreatProduct drum used for other chemical Check Nitrite level of the product or take a new product drumpH Coolingwater too low Bacteria in the systemLow Caretreat 2 Diesel dosageCheck for slime deposits Add a non corrosive biocide, CaretreatCheck dosing pump/increase dosagepH Coolingwater too highHigh Caretreat 2 Diesel dosageCheck dosing pump/decrease dosage Refresh the system partly with demineralized or evaporated water
-
Partslist Boiler- and Coolingwater Testkit Partslist Boiler- and Coolingwater Testkit Amount pH strips (100 ea.) 7,0 - 14,0 1 Description Amount Reagent BC1 1 pH strips (100 ea.) 7,0 - 14,0 1 pH strips (100 ea.) 0,0 - 14,0 1 Reagent BC1 1 Reagent BC2 1 Reagent N1 1 Reagent N2 1 Reagent PA1 1 Reagent PA2 1 Syringe, 20 ml 1 Syringe, 1 ml 1 -
- Read the boilers manual regarding the boilerwater systems treatment
- Read the engines manual regarding the coolingwater systems treatment
- Contact us for advise
- E-mail us all test figures over a period of at least 3 months
- Use E-care monitoring program
- Samples Boilerwater
- Send us a Boilerwater and Feedwater sample
- Take a sample in a clean bottle at least 0,5 liter per sample — Fill the bottle(s) to the top
- Samples Coolingwater
- Send us a Coolingwater and Make-up water sample
- Take a sample in a clean bottle at least 0,5 liter per sample — Fill the bottle(s) to the top